Worcester Greenstar Highflow 440CDi Boiler Fault Codes

 Code Description Check, repair/replace as necessary
A1 Pump dry run detection or Pump is running in air Check the system pressure, refill if necessary
A5 Tank NTC defect Check tank NTC sensor and leads, measure resistance across NTC (33.5k- 500)
A7 DHW NTC defect Check DHW NTC sensor and leads, measure resistance across NTC (33.5k- 500)
A8 EMS communication error Check electrical connections of EMS controls (if fitted), connections on the control board, replace control board.
b1 Code plug not detected Insert code plug correctly, test and replace as necessary.

b2,b3,b4,

b5,b6

Data error Replace control board.
b7 Burner control error Replace control board.
C6 Fan defect Check fan, lead, and connector, replace as necessary.
D3 External temp limiter Check plug connector ST8, link missing/damaged between 8 & 9 on ST8 .
D5 Condensate pump failure See condensate pump table.
D6 Internal heat bank overflow Check system pressure, tank over heat thermostat and leads, and pump operation
EA Flame not detected Check gas is present and working gas pressure, ignition electrodes and harness, flame sense electrode and harness, and operation of gas valve. Replace as necessary.
E2 Primary NTC defect Check primary NTC sensor and leads, resistance across NTC should be between 36k to 1k
E9 OH stat tripped

Check system pressure, over heat thermostat, and pump operation.

Check fuse (T1.6A slow blow), replace as necessary.

F0 Internal error Check all electrical connections, replace board as necessary.
F1 ROM error check Check all electrical connections, replace board as necessary.
F7 Flame detected after appliance shut off Check flame sense electrode and harness, and control board for signs of water damage. Replace as necessary
FA Flame detected after gas shut off Check flame sense electrode and harness, and control board for signs of water damage. Check gas valve operation. Replace as necessary
Fd Reset button pressed Press reset button again