Worcester Greenstar FS30 ErP regular LPG Boiler Fault Codes

 Code Description Check, repair/replace as necessary
A8 EMS coms error Check all electrical connections, replace control board.
b1 Code plug not detected Insert code plug correctly, test and replace as necessary.

b2,b3,b4,

b5,b6

Data error Replace control board.
b7 Burner control error Replace control board.
C6 Fan defect check fan, lead and connector. Replace as necessary
d3 External temp limiter Connect terminals 8 & 9 on ST8.
d5 Condensate pump failure see condensate pump table
EA Burner control lockout Check gas is present, ignition electrodes and harness, flame sense electrode and harness, and operation of gas valve. Replace as necessary.
E2 Primary NTC defect Check primary NTC sensor and leads, resistance across NTC should be between 36k to 1k Ω
E9 OH stat tripped Check system pressure, overheat thermostat, and pump operation. Replace as necessary
F0 Internal error Check all electrical connections, replace control board as necessary.
F1 ROM error check Check all electrical connections, replace control board as necessary.
F7 Flame detected after appliance shut off Check flame sense electrode and harness, and control board for signs of water damage. Replace as necessary
FA Flame detected after gas shut off Check flame sense electrode and harness, and control board for signs of water damage. Check gas valve operation. Replace a s necessary
Fd Reset button pressed press reset button again.