Worcester Greenstar CDi 30 Conventional LPG Boiler Fault Codes

 Code Description Remedy
b1 Code plug not detected Insert code plug correctly, test and replace if necessary
C6 Fan speed too low Check fan lead and connector, and fan; replace as necessary
E2 flow NTC sensor defective Check flow NTC sensor and connecting lead
E9 Safety temp. limiter in flow has tripped Check system pressure, check safety temp. limiters, check pump operation, check fuse on pcb, bleed appliance.
EA Flame not detected Is gas cock turned on? Check gas supply pressure, power supply, igniter electrode and lead, ionisation sensing electrode and lead, flue duct and CO2 level.
F0 Internal error Check electrical connector contacts, programmer interface module ignition leads are not loose; replace pcb if necessary
F7 Flame detected even though appliance switched off Check electrode assembly, dry pcb. Flue clear?
FA Flame detected after gas shut off Check gas valve and wiring to gas valve. Clean condensation trap and check electrode assembly. Flue clear?
Fd Reset button pressed by mistake Press reset button again.