Worcester Greenstar 8000 Life GR8300iW 40R Lpg Boiler Fault Codes

 

 Code Category Description Remedy
200 O Boiler in heating mode -
201 O Boiler in hot water mode -
202 O Boiler in anti-cycle mode -
203 O Boiler in standby, no heat energy demand -
204 O Current prim. water temp. higher than set val. -
208 O Chimney sweep demand -
224 V Safety temp. limiter has tripped

1. Open the closed valve in the heating circuit.

2. Top up water until the preset pressure is reached.

3. Connect the plug correctly to the safety temperature limiter.

4. Replace the safety temperature limiter.

227 V No flame signal after ignition

1. Open the gas isolator.

2. Change the gas installation.

3. Replace the control unit/burner control unit.

4. Replace the ignition electrode.

5. Replace the monitoring electrode.

6. Replace the ignition cable.

7. Replace the ionisation cable.

8. Replace the air/gas ratio control valve.

9. Correct the burner setting.

228 V Flame signal without flame present

1. Replace the air/gas ratio control valve.

2. Replace the ionisation cable.

3. Replace the control unit/burner control unit.

306 V Flame signal after closing the fuel supply

1. Replace the air/gas ratio control valve.

2. Replace the ionisation cable.

3. Replace the control unit/burner control unit.

360 V Incompatible code plug

1. Check if a correct code plug is installed.

2. Exchange or reconnect code plug.

815 W Low loss header temp. sensor faulty

1. Check the sensor port.

2. Check the differential sensor for incorrect installation position or breakage.

1010 O No BUS communication. Cable for EMS-Bus is not correct connect or damaged.

1. Connect the cable for the EMS-Bus correct or replace the damaged cable.

2. Exchange fuse

1037 W Outside temperature sensor defective The control panel is receiving unrealistic values from the outside sensor. Effect: The minimum outside temperature is used.
1068 W Outside temperature sensor defective Outdoor temperature sensor is defective.
1073 W Short circuit of the flow temperature sensor

1. Replace the temperature sensor.

2. Replace the connecting lead to the temperature sensor.

3. Replace the control unit.

1074 W No signal from the flow temperature sensor available

1. Connect the plug to the flow temperature sensor correctly.

2. Replace the flow temperature sensor.

3. Replace the connecting lead to the flow temperature sensor.

4. Replace the control unit.

1075 W Short circuit of the temperature sensor at the heating block

1. Replace the temperature sensor.

2. Replace the connecting lead to the temperature sensor.

3. Replace the control appliance.

1076 W No signal from the temperature sensor at the heating block available

1. Replace the temperature sensor.

2. Replace the connecting lead to the temperature sensor.

3. Replace the control unit.

2920 V Fault in flame monitoring

Igniter on for too long after flame detected:

1. Check cabling.

2. Check igniter.

3. Check burner module.

2924 V No feedback from the modulating gas valve

Gas valve relay defect.

1. Press Reset button and apply burner start. Wait to see if fault reoccurs.

2. Replace the gas valve.

2925 V Too low feedback from the modulating gas valve Too low feedback from the modulating/current controlled gas valve.
2927 B Flame failed during burner operation

1. Open the main shut-off valve.

2. Open the appliance shut-off valve.

3. Shut down the appliance and check the gas line.

4. Signal evaluation on printed circuit board defective.

5. Replace the ionisation electrode.

6. Establish protective conductor connection (PE) in the control unit.

7. Replace the ignition cable.

8. Replace the connecting lead to the ionisation electrode.

9. Replace the air/gas ratio control valve.

10.Set the burner correctly.

11.Set the burner at minimum rated load.

12.Check the integrity flue system.

13.Clean the heating block on the flue gas side.

14.Replace the control unit/burner control unit.

2946 V Incorrect code plug detected Replace the code plug.
2948 B No flame signal with low output

The burner starts automatically after cleaning.

1. If the fault occurs repeatedly: check the settings of the CO2 values.

2950 B No flame signal following starting procedure

The burner starts automatically after cleaning.

1. Set the correct gas/air ratio correctly.

2963 B Signal from flow and heat exchanger temperature sensor outside the permissible range Connect the connecting lead correctly.
2964 B Flow rate in heat exchanger too low

1. Supply sensor is not assembled on the supply pipe.

2. Supply sensor does not make proper contact to the supply pipe.

3. System is not filled with water.

4. No water flow, because CH system is closed.

5. No water flow, because pump is not operating correctly.

2965 B Flow temperature too high

1. System is not filled with water.

2. No water flow, because CH system is closed.

3. No water flow, because pump is not operating correctly.

2966 B Flow temperature rise in heat exchanger too rapid

1. System is not filled with water.

2. No water flow, because CH system is closed.

3. No water flow, because pump is not operating correctly.

2967 B Flow/heat exchanger temperature sensor differential too great

1. Supply sensor is not assembled on the supply pipe.

2. Supply sensor does not make proper contact to the supply pipe.

3. System is not filled with water.

4. No water flow, because CH system is closed.

5. No water flow, because pump is not operating correctly.

 Appliance Faults Remedy
Combustion noises too loud; rumbling noises

▶ Check the gas type.

▶ Check the gas supply pressure. ]

▶ Check the flue system; clean or repair if required.

▶ Check the gas/air ratio.

▶ Check the air/gas ratio control valve; replace if required.

Flow noises ▶ Set the pump rate or pump characteristic map correctly and match to the maximum output.
Heat-up takes too long. ▶ Set the pump rate or pump characteristic map correctly and match to the maximum output.
Flue gas values incorrect; CO content too high

▶ Check the gas type.

▶ Check the gas supply pressure.

▶ Check the flue system; clean or repair if required.

▶ Check the gas/air ratio.

▶ Check the air/gas ratio control valve; replace if required.

Delayed ignition, poor ignition.

▶ Check the ignition transformer with service function t01 for misfiring, replace if required.

▶ Check the gas type.

▶ Check the gas supply pressure.

▶ Check the power supply.

▶ Check the electrodes with cable; replace if required.

▶ Check the flue system; clean or repair if required.

▶ Check the gas/air ratio.

▶ For natural gas: check the external gas flow monitor, replace if required.

▶ Check the burner, replace if required.

▶ Check the air/gas ratio control valve; replace if required.

Condensate in air box ▶ Check the non-return valve in the air gas manifold, replace if required.
No function, the display remains dark.

▶ Check the electrical wiring for damage.

▶ Replace defective cables.

▶ Check the fuse, replace if required.