Worcester Greenstar 42 CDI Classic ErP Boiler Fault Codes

 Code Description Remedy
A1 Pump has run dry or pump has stalled/seized

Check for water leaks.

Free the pump or replace

A7 Hot water NTC sensor defective.

Check:

- hot water NTC sensor

- connecting lead for circuit breaks/short circuits.

A8 Break in communication to FX/Sense controls Check electrical connections.
b1 Code plug not detected. Insert code plug correctly, test and replace if necessary
C6 Fan speed too low.

Check:

fan lead and connector, and fan; replace as necessary.

E2 CH flow NTC sensor defective. Check CH flow NTC sensor and connecting lead.
E9 Safety temp. limiter in CH flow has tripped.

Check:

- system pressure,

- safety temp. limiters,

- pump operation,

- fuse on pcb, bleed appliance.

EA Flame not detected.

Is gas cock turned on?

Check:

- gas supply pressure,

- power supply,

- igniter electrode and lead,

- ionisation sensing electrode and lead,

- flue duct and CO2 level.

F0 Internal error. Check electrical connector contacts, programmer interface module ignition leads are not loose; replace pcb if necessary.
F7 Flame detected even though appliance switched off.

Check:

- electrode assembly,

- dry pcb.

- Flue clear?

FA Flame detected after gas shut off.

Check:

- gas valve; resistance, coil 1 = 190, coil 2 = 390

- wiring to gas valve. Clean condensate trap and check electrode assembly.

Flue clear?

Fd Reset button pressed by mistake. Press reset button again