Worcester Greenstar 24Ri LPG Boiler Fault Codes

 Indication Fault Possible solution
No light Permanent mains supply to boiler. Boiler mains switch on. Fuse F1. Fuse F2. Transformer (both coils below 100Ω). Otherwise replace control board (if boiler does not operate correctly).
Light on but boiler not operating during demand Boiler demand live at ST2 terminal LR (is there a demand) By pass is open If either only HW or CH is operating check diverter valve/frost stat/ room stat/programmer. Otherwise replace control board.
*Slow flash (normally off, flashes on) Ignition lockout Gas present and at correct pressure. Combustion CO2 level. Flue condition Ignition electrodes/cables/connections Flame sense electrode/cables/connections Gas valve (coils 140-190Ω). Otherwise replace control board.
*Slow flash (normally on, flashes off)

Flue overheat

Heat exchanger overheat

Flue pressure switch

Flue temperature too high. Heat exchanger baffles have been removed and not refitted.

Water pressure/dry All air vented Pump/cables/connections Water leaks/blockages Safety thermostats/cables/connections Otherwise replace control board

Blockage in flue system

Fast flash Volatile lockout (sensor, fan or code plug) Temperature sensor (8000 - 20000Ω). Wiring/connections to sensor. Fan/cable/connections. Code plug fitted.
2 pulses Service mode switch in min position.
5 pulses Service mode switch in min position.