Worcester Commercial GB 162-50/65/80/100 Boiler Fault Codes

 Main Display Code Sub Display Code Key to display code Reset required? LED on UBA 3 Other effects
- Operating phase: Communication test while starting up. This display code flashes 5 times within 5 seconds while starting up to indicate that the communication between the UBA 3 and the BC10 basic controller is being tested. If a new UBA 3 or a new KIM was fitted, this code will flash for max. 10 seconds. Off or flashing at 8 Hz
-

Fault:

If this code continues to flash on the display, there is a fault in the communication between the UBA 3 and the BC10 basic controller.

Off or flashing at 8 Hz
A 208 Operating phase: The boiler is in flue gas test or service mode. Off or flashing at 8 Hz No heating operation and no DHW.
H 200 Operating phase: The boiler is in heating mode Off
H 200 Operating phase: The boiler is in manual operation mode. Off The room temperature is too high.
H 201 Operating phase: The boiler is in DHW mode. Off
H 201

Operating phase:

Pump run-over time via the external hot water cylinder 130 seconds at the minimum speed. The “Burner” LED (On/Off) is off.

Off
0A 202

Operating phase:

The switch optimization program is activated. This program is activated if there has been any demand more frequently than once every 10 minutes. This means that the boiler cannot be restarted until at least 10 minutes have elapsed since initial burner start-up.

Off The room temperature is not possibly reached.
0A 305 Operating phase: The boiler cannot start up temporarily after a DHW request has ended. Off
0C 283 Pre-operative phase: The boiler prepares for a burner start-up whenever a heat demand or a DHW request arises. Off
0E 265 Readiness for operation: The boiler is in standby mode. There is a current heat demand, but too much energy has been supplied. Off
0H 203 Readiness for operation: The boiler is in standby mode. There is no current heat demand. Off
0L 284 Ignition phase: The gas valve is activated. Off
0U 270 Start-up phase: The boiler starts up after activation of the mains power supply or completion of a system reset. This code is displayed for a maximum of 4 minutes. Off
0Y 204 Operating phase: The flow temperature sensor has detected that the current flow temperature is higher than the flow temperature setting on the BC10, or that it is higher than the flow temperature. Calculated according to heating requirements, or that it is higher than the flow temperature calculated for the DHW mode. Off The room temperature is not possibly reached.
0Y 276 Fault: The flow temperature sensor has measured a current flow temperature higher than 95 °C. No Off The room temperature is not possibly reached.
0Y 277 Fault: The safety temperature sensor has measured a current safety temperature higher than 95 °C. No Off The room temperature is not possibly reached.
0Y 285 Fault: The return temperature sensor has measured a current return temperature higher than 95 °C. No Off The room temperature is not possibly reached.
1L 211 Fault: There is no connection between contacts 78 and 50 of the UBA 3 installation base. No Off The room temperature is not possibly reached.
2E 207 Fault: The system pressure is too low (less than 0.2 bar). No Off The room temperature is not possibly reached.
2F 260 Fault: The flow temperature sensor has not, after burner start-up, detected any temperature increase in the heating system water. No Off
2F 271 Fault: The heating water temperature difference, measured between the flow temperature sensor and the safety temperature sensor, is too high.
2P 212 Fault: The flow temperature sensor has measured a heating water temperature increase of over 5 °C/s. No Off
2U 213 Fault: The temperature difference measured between the flow temperature sensor and the return temperature sensor, is more than 50 °C. No Off
2Y 281 Fault: The pump has stopped or is running without water. No Off
2Y 282 Fault: No feedback from the pump. No Off
3A 264 Fault: The tacho signal from the fan has failed during the operating phase. No Off
3C 217 Fault: No current of air after a certain time. Yes flashing 1 Hz No heating operation and no DHW.
3F 273 Operating phase: The appliance has been switched off for a couple of seconds, because it had been running without any interruption for 24 hours. This is a safety check. No Off
3L 214 Fault: The tacho signal from the fan is not present during the pre-operative or operating phase. Yes flashing 1 Hz No heating operation and no DHW.
3P 216 Fault: The fan is running too slowly. Yes flashing 1 Hz No heating operation and no DHW.
3Y 215 Fault: The fan is running too fast Yes flashing 1 Hz No heating operation and no DHW.
4A 218 Fault: The flow temperature sensor has detected a flow temperature of over 105 °C. Yes flashing 1 Hz No heating operation and no DHW.
4C 224 Fault: There is no bridging cable between contacts 22 and 24 of the UBA 3 contact strip. Yes flashing 1 Hz No heating operation and no DHW.
4E 278 Fault: The sensor test has failed. Yes flashing 1 Hz No heating operation and no DHW.
4F 219 Fault: The safety temperature sensor has detected a flow temperature of over 105 °C. Yes flashing 1 Hz No heating operation and no DHW.
4L 220 Fault: The contacts for the safety temperature sensor have shorted or the safety temperature sensor has detected a flow temperature of over 130 °C. Yes flashing 1 Hz No heating operation and no DHW.
4P 221 Fault: The contacts for the safety temperature sensor have shorted. Yes flashing 1 Hz No heating operation and no DHW.
4U 222 Fault: The contacts for the safety temperature sensor have shorted. Yes flashing 1 Hz No heating operation and no DHW.
4Y 223 Fault: The contacts for the safety temperature sensor have shorted. Yes flashing 1 Hz No heating operation and no DHW.
5H 268 Operating phase: Component test phase. No Off
6A 227 Fault: The system has detected an insufficient ionisation current during the ignition phase. No Off
6A 227 Fault: The system has detected an insufficient ionisation current after four start-up attempts. Yes flashing 1 Hz No heating operation and no DHW.
6C 228 Fault: The system has detected an ionisation current before burner start-up. Yes flashing 1 Hz No heating operation and no DHW.
6C 306 Fault: An ionisation current has been measured after the burner shut down. Yes flashing 1 Hz No heating operation and no DHW.
6L 229 Fault: The system has detected an insufficient ionisation current during the operating phase. No Off
6P 269 Fault: The glow ignitor was activated for more than 10 minutes. Yes flashing 1 Hz No heating operation and no DHW.
6Y 203 Fault: The ionisation current is too high. Yes flashing 1 Hz No heating operation and no DHW.
7C 231 Fault: The power supply was interrupted during a locking fault 4A, 4C, 4E, 4F, 4L, 4P, 4U, 4Y. Yes flashing 1 Hz No heating operation and no DHW.
7L 261 Fault: The UBA 3 is defect. Yes flashing 1 Hz No heating operation and no DHW.
7L 280 Fault: The UBA 3 is defect. Yes flashing 1 Hz
8Y 232 Operating phase: The external switch contact is open. Off No heating operation and no DHW.
888 Start-up phase: The boiler starts up after activation of the mains power supply or completion of a system reset. This code is displayed for a maximum of 4 minutes. On
9A 235 Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz No heating operation and no DHW.
9H 237 Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz No heating operation and no DHW.
9H 267 Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz No heating operation and no DHW.
9H 272 Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz No heating operation and no DHW.
9L 234 Fault: The contacts for the gas valve have been broken. Yes flashing 1 Hz No heating operation and no DHW.
9L 238 Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz
9P 239 Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz No heating operation and no DHW.
9U 233 Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz No heating operation and no DHW.
A01 800 Fault: The contacts to the outdoor-temperature sensor have shorted or are interrupted, the sensor has been connected incorrectly or is defective. No Off Minimum outdoor temperature is assumed.
A01 808 Fault: The contacts to the DHW temperature sensor have shorted or are interrupted, the sensor has been connected incorrectly or is defective. No Off No DHW is heated any more.
A01 809 Fault: The contacts to DHW temperature sensor 2 have shorted or are interrupted, the sensor has been connected incorrectly or is defective. No Off No DHW is heated any more.
A01 810 Fault: The boiler water does not warm up. Sensor lead broken or shorted, sensor connected incorrectly or defective, filling pump connected incorrectly or defective. No Off No DHW available, but there is heating operation. The DHW priority is cancelled when the fault message appears.
A01 811 Fault: Thermal disinfection has failed. Outlet flow during disinfection period too high, sensor lead broken or shorted, sensor connected incorrectly or defective, filling pump defective. No Off Thermal disinfection was interrupted.
A01 816 Fault: No connection to EMS. EMS bus system is overloaded, UBA3/MC10 is defective. No Off The boiler no longer receives a heat demand. The heating system does not heat any longer.
A01 828 Fault: Water pressure sensor generates a fault code. The digital water pressure sensor is defective. No Off No heating operation and no DHW.
A02 816 Fault: No communication with BC10. Contact problem at BC10 or BC10 is defective. No Off BC10 settings are no longer taken over by RCxx devices.
A11 802 Fault: Time not set. Failing time setting, e.g. due to a long power cut. No Off Limited operation of all heating programs and fault list.
A11 803 Fault: Date not set. Failing date setting, e.g. due to a long power cut. No Off Limited operation of all heating programs, holiday function, fault list.
A11 821 Fault: RC35-HK1 remote control. No remote control assigned, although room temperature control has been set. No Off Limited operation of all heating programs, holiday function, fault list.
A11 822 Fault: RC35-HK2 remote control. No remote control assigned, although room temperature control has been set. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work. The EMS works on the basis of the values last set on the remote control.
A11 823 Fault: RC35-HK1 remote control. No remote control assigned, although frost protection type “FROST” has been set. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work. The EMS works on the basis of the values last set on the remote control.
A11 824 Fault: RC35-HK2 remote control. No remote control assigned, although frost protection type “FROST” has been set. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work. The EMS works on the basis of the values last set on the remote control.
A11 826 Fault: RC35-HK1 temperature sensor. The external temperature sensor of the remote control (control unit) of heating circuit 1 is defective. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work. The EMS works on the basis of the values last set on the remote control.
A11 827 Fault: RC35-HK2 temperature sensor. The external temperature sensor of the remote control (control unit) of the heating circuit is defective. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work. The EMS works on the basis of the values last set on the remote control.
A12 815 Fault: The contacts to the switch sensor have shorted or are interrupted, the sensor has been connected incorrectly or is defective. No Off Limited operation of all heating programs, holiday function, fault list.
A12 816 Fault: WM10 not available or no communication. WM10 or bus circuit connected incorrectly or defective, WM10 is not recognized by the RC35. No Off Heating circuit pump 1 is activated continuously.
A18 825 Fault: Conflicting addresses. Both RC25 and RC35 are registered as Master. No Off Both RC35 and RC25 activate heating circuit 1 and DHW. Depending on the heating programs set and the required room temperatures, the heating system can no longer work correctly. DHW mode does not work well.
A21 806 Fault: RC25-HK1 temperature sensor. The integrated temperature sensor of the remote control (control unit) of heating circuit 1 is defective. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work. The EMS works on the basis of the values last set on the remote control.
A21 816 Fault: RC25-HK1 communication. RC25 addressed incorrectly, wired incorrectly or defective. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work.
A22 806 Fault: RC25-HK2 temperature sensor. The integrated temperature sensor of the remote control (control unit) of heating circuit 2 is defective. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work. The EMS works on the basis of the values last set on the remote control.
A22 816 Fault: RC25-HK2 communication. RC25 addressed incorrectly, wired incorrectly or defective. No Off Since there is no actual room temperature information, room influence and optimization of the switch times do not work.
A32 807 Fault: The contacts to the heating circuit flow sensor have shorted or are interrupted, the sensor has been connected incorrectly or is defective. No Off Heating circuit pump 2 is activated depending on the preset value. The power to the mixer is switched off and the mixer stays in the state it was last put in (can be adjusted manually).
A32 816 Fault: MM10 not available or no communication. The heating circuit addresses on the MM10 and the RC35 do not match up, the MM10 or the bus circuit is connected incorrectly or is defective, MM10 is not recognized by the RC35. No Off Heating circuit 2 cannot be operated correctly. MM10 and the mixer automatically goes into emergency operation. Heating circuit pump 2 is activated continuously. Monitor data in the RC35 is invalid.
CA 286 Fault: The return temperature sensor has measured a return temperature higher than 105 °C. Yes flashing 1 Hz No heating operation and no DHW.
CU 240 Fault: The contacts for the return temperature sensor have shorted. Yes flashing 1 Hz No heating operation and no DHW.
EL 290 Fault: The UBA 3 or the KIM is defective. No Off No heating operation and no DHW.
E

242

287

Fault: The UBA 3 or the KIM is defective. Yes flashing 1 Hz No heating operation and no DHW.
H7 Operating phase: The system pressure is too low (less than 1.0 bar). No Off Possibly no heating operation or no DHW available.
H7 Operating phase: The system pressure is too low (less than 1.0 bar). No Off Possibly no heating operation or no DHW available.
P-- Operating phase: The system pressure is too high (over 4.0 bar) or the pressure sensor has not detected a system pressure (boiler functioning normally). No Off
rE Fault: Reset is carried out. After pressing the “Reset” button this code is displayed for 5 seconds. Off