Vaillant ecoTEC pro 28 LPG Boiler Fault Codes

Vaillant Boilers
 Code Meaning Cause
F00 Flow temperature sensor interruption NTC plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, NTC defective
F01 Return temperature sensor interruption NTC plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, NTC defective
F10 Flow NTC short circuit NTC defective, short circuit in cable harness, cable/casing
F11 Return NTC short circuit NTC defective, short circuit in cable harness, cable/casing
F20 Safety switch-off: temperature limiter Incorrect earth connection between cable harness and boiler, flow or return NTC defective (loose connection), black discharge via ignition cable, ignition plug or ignition electrode
F22 Safety switch-off: low water pressure No or to low water pressure in the boiler, water pressure sensor defective, cable to pump or water pressure sensor loose/not connected/defective
F23 Safety switch-off: Temperature difference too great Pump blocked, insufficient pump output, air in boiler, flow and return NTC interchanged
F24 Safety switch-off: Temperature rise too fast Pump blocked, poor pump performance, air in boiler, system pressure too low, non-return valve blocks/incorrectly installed
F25 Safety switch-off: Flue gas temperature too high Break in plug connection for optional flue gas safety thermostat (STB), break in cable harness
F26 Fault: Gas valve without function Gas valve stepper motor not connected, multiple plug on the PCB not plugged in correctly, interruption in cable harness, gas valve stepper motor defective, electronics defective
F27 Safety switch-off: Flame simulation Moisture on the electronics, electronics (flame monitor) defective, gas solenoid valve leaking
F28 Failure during start-up: ignition unsuccessful Gas meter defective or gas pressure regulator has triggered, air in gas, gas flow pressure too low, thermal isolator device (TAE) has triggered, condensate duct blocked, incorrect gas restrictor, incorrect ET gas valve, fault on the gas valve, multiple plug on PCB incorrectly plugged in, break in cable harness, ignition system (ignition transformer, ignition cable, ignition plug, ignition electrode) defective, ionisation current interrupted (cable, electrode), incorrect earthing of boiler, electronics defective
F29 Failure during operation: Re-ignition unsuccessful Gas supply temporarily stopped, flue gas recirculation, condensate duct blocked, faulty earthing of boiler, ignition transformer has spark failure
F32 Fan fault Plug at fan not correctly plugged in, multiple plug on PCB not correctly plugged in, break in cable harness, fan blocked, Hall sensor defective, electronics defective
F49 eBUS fault Short circuit on eBUS, eBUS overload or two power supplies with different polarities on the eBUS
F61 Gas valve actuation fault

The gas valve cannot be actuated

– Cable harness supply line to the gas valve is defective (short to earth, short circuit)

– Gas valve defective

– PCB defective

F62 Fault: Gas valve switch-off delay

Delayed shutdown of gas valve detected

– Secondary light (ignition and monitoring electrode indicates delayed extinguishing of the flame signal)

– Gas valve defective

– PCB defective

F63 EEPROM error Electronics defective
F64 Electronics/NTC fault Flow or return NTC short circuited, electronics defective
F65 Electronic temperature fault Electronics overheating due to external influences, electronics defective
F67 Electronics/flame fault Implausible flame signal, electronics defective
F68 Unstable flame signal fault Air in gas, gas flow pressure too low, wrong air ratio, condensate route blocked, wrong gas restrictor, ionisation flow interruption (cables, electrodes), flue gas recirculation, condensate route
F70 Invalid device specific number (DSN) Spare part case: Display and PCB replaced at same time and DSN not set, wrong or missing output range coding resistor
F71 Flow NTC fault

Flow temperature sensor signalling constant value:

- Flow temperature sensor incorrectly positioned at supply pipe.

- Flow temperature sensor defective.

F72 Flow/return NTC fault Flow/return NTC temperature difference too great -> flow and/or return temperature sensor defective
F73 Water pressure sensor signal in the wrong range (too low) Interruption/short circuit of water pressure sensor, interruption/short circuit to GND in supply line to water pressure sensor or water pressure sensor defective
F74 Water pressure sensor signal outside correct range (too high) Cable to water pressure sensor has short-circuited at 5 V/24 V or internal fault in water pressure sensor
F75 Fault, no pressure change detection when starting pump Water pressure sensor and/or pump defective, air in heating installation, too low water pressure in boiler; check adjustable bypass, connect external expansion vessel to return
F77 Flue non-return flap/condensate pump fault No response from flue non-return flap or condensate pump defective
F78 Interruption to DHW outlet sensor at external controller UK link box is connected, but hot water NTC not bridged
F83 Flow and/or return temperature sensor temperature change fault

When the burner starts, the temperature change registered at flow and/or return temperature sensor is non-existent or too small.

- Not enough water in the boiler

- Flow and/return temperature sensor not in correct position at pipe.

F84 Fault: Flow/return temperature sensor temperature difference implausible

Flow and return temperature sensors returning implausible values.

- Flow and return temperature sensors have been inverted.

- Flow and return temperature sensors have not been correctly fitted.

F85 Fault: Flow and return temperature sensors incorrectly fitted Flow and/or return temperature sensors have been fitted to the same pipe/wrong pipe.
Communication fault No communication with the PCB Communication fault between display and PCB in the electronics box