Vaillant ecoFitpure 430 Boiler Fault Codes

Vaillant Boilers
 Code Meaning Cause
F00 Flow temperature sensor interruption NTC plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, NTC defective
F01 Return temperature sensor interruption NTC plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, NTC defective
F10 Flow NTC short circuit NTC defective, short circuit in cable harness, cable/casing
F11 Return NTC short circuit NTC defective, short circuit in cable harness, cable/casing
F13 Warm start sensor/cylinder sensor short circuit NTC defective, short circuit in cable harness, cable/casing
F22 Safety switch-off: Low water pressure No or insufficient water in the product, water pressure sensor defective, cable to pump or water pressure sensor loose/not connected/defective
F23 Safety switch-off: Temperature difference too great Pump blocked, insufficient pump output, air in product, flow and return NTC connected the wrong way round
F24 Safety switch-off: Temperature rise too fast Pump blocked, insufficient pump output, air in product, system pressure too low, non-return valve blocked/incorrectly installed
F25 Safety switch-off: Flue gas temperature too high Break in plug connection for optional flue gas safety temperature limiter (STB), break in cable harness
F27 Safety switch-off: Flame simulation Moisture on the electronics, electronics (flame monitor) defective, gas solenoid valve leaking
F28 Failure during start-up: Ignition unsuccessful Gas meter defective or gas pressure monitor has triggered, air in gas, gas flow pressure too low, thermal isolator device (TAE) has triggered, condensate duct blocked, incorrect gas restrictor, incorrect spare part gas valve, fault on the gas valve, multiple plug on PCB incorrectly plugged in, break in cable harness, ignition system (ignition transformer, ignition cable, ignition plug, ignition electrode) defective, ionisation current interrupted (cable, electrode), incorrect earthing of product, electronics defective
F29 Failure during operation: Re-ignition unsuccessful Gas supply temporarily stopped, flue gas recirculation, condensate duct blocked, defective earthing of product, ignition transformer has spark failure
F32 Fan fault Plug on fan not correctly plugged in, multiple plug on PCB not correctly plugged in, break in cable harness, fan blocked, Hall sensor defective, electronics defective
F49 Fault: eBUS Short circuit on eBUS, eBUS overload or two power supplies with different polarities on the eBUS
F61 Fault: Gas valve regulation

- Short circuit/short to earth in cable harness for the gas valve

– Gas valve defective (coils shorted to earth)

– Electronics defective

F62 Fault: Gas valve switch-off delay

– Delayed shutdown of gas valve

– Delayed extinguishing of flame signal

– Gas valve leaking

– Electronics defective

F63 Fault: EEPROM Electronics defective
F64 Fault: Electronics/NTC Flow or return NTC short circuited, electronics defective
F65 Fault: Electronics temp. Electronics overheating due to external influences, electronics defective
F67 Fault: Electronics/flame Implausible flame signal, electronics defective
F68 Fault: Unstable flame signal Air in gas, gas flow pressure too low, incorrect air ratio, condensate duct blocked, incorrect gas restrictor, ionisation flow interruption (cable, electrode), flue gas recirculation, condensate duct
F70 Invalid device specific number (DSN) If spare parts fitted: Display and PCB replaced at same time and DSN not reset, incorrect or missing output range coding resistance
F71 Flow NTC fault

Flow temperature sensor signalling constant value:

– Flow temperature sensor incorrectly positioned at supply pipe

– Flow temperature sensor defective

F72 Flow/return NTC fault Flow/return NTC temperature difference too great → flow and/or return temperature sensor defective
F73 Water pressure sensor signal in the wrong range (too low) Interruption/short circuit of water pressure sensor, interruption/short circuit to GND in supply line to water pressure sensor or water pressure sensor defective
F74 Water pressure sensor signal outside correct range (too high) Line to water pressure sensor has a short circuit to 5 V/24 V or internal fault in the water pressure sensor
F75 Fault: No pressure change detection when starting pump Water pressure sensor and/or pump defective, air in the heating installation, insufficient water in the product; check adjustable bypass, connect external expansion vessel to the return
F76 Overheating protection on primary heat exchanger has responded Cable or cable connections for safety fuse in primary heat exchanger or primary heat exchanger defective
F77 Fault: Flue non-return flap/condensate pump No response from flue non-return flap or condensate pump defective
F83 Fault: Flow and/or return temperature sensor temperature change

When the burner starts, the temperature change registered at the flow and/or return temperature sensor is non-existent or too small.

– Insufficient water in product

– Flow or return temperature sensor not in correct position at pipe

F85 Fault: Flow and return temperature sensors incorrectly installed The flow and/or return temperature sensors have been installed on the same pipe/incorrect pipe
F87 Ignition transformer not connected Ignition transformer plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, electronics defective
F88 Gas valve not connected Gas valve plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, electronics defective
F89 Incorrect pump detected Unsuitable pump connected, PWM plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, electronics defective
con No communication with the PCB Communication fault between display and PCB in the electronics box