Worcester Greenstar Heatslave External 12/18 Boiler Fault Codes

BOILER LOCKOUT : Indicated by the illumination of the 'Lockout' indicator on the fascia. To reset, wait 2 minutes then press the lockout reset button.
 Problem Cause Remedy
Pulsation on start

Combustion settings incorrect

Faulty nozzle

Set up as in installation instructions

Replace nozzle

Intermittent lockout

Bad electrical connection

Intermittent flame detection fault

Check control box/electrical connections

See flame detection fault

Burner motor fails to operate

Faulty motor or electrical supply to motor

Control box fault

Check for 230v at motor plug during startup period

Replace control box

Flame detection fault

Photocell filmed over (dirty)

Photocell faulty

Control box faulty

Wipe clean

Replace

Replace

Incorrect CO2

Air adjustment fault

Oil pressure incorrect

Set up as in installation instructions

Set up as in installation instructions

No oil from nozzle

No oil at pump

Air in pump

Nozzle blocked

Faulty pump or drive

Faulty mechanical shut off valve

(12/18 & 18/25 only)

Check and refill oil tank/bleed oil line. Check and clean filters & valves from oil tank to boiler.

Bleed pump

Replace nozzle

Replace

Clean or replace

 

Ignition failure

Electrode settings incorrect

Faulty ignition transformer

Open circuit ignition

Faulty control box or electrical connections not properly made

 

Set up as in installation instructions

Replace

Check and replace electrodes or high tension leads if necessary

Correct control box electrical connections or replace control box

 

Burner fails to start

 

No power to boiler

Faulty boiler thermostat

Programmer open circuit

Faulty control box

Check electrical / control circuit

Check by temporarily linking out high limit and control thermostats

Check by temporarily linking 8 & 9 on the connector

Replace

High smoke number

Air intake/flue blocked

Incorrect combustion settings

Oil pressure incorrect

Incorrect components used on combustion head

Faulty nozzle

 

Check & clear air intake/flue

Set up as in installation instructions

Adjust to correct pressure

Check with installation instructions

Replace nozzle

Noisy operation

Pump noise from air in pump or worn pump

Worn motor bearings

Fan out of balance

Bleed air from pump or replace pump

Replace motor

Replace fan

Boiling

Faulty boiler thermostat

Short circuit boiler thermostat

Thermostat bulb not fully home in pocket

No primary water circulation

Replace if necessary

Take out of circuit to check

Ensure bulb is pushed fully home

Check system / circulating pump

Short Cycling

Burner rating incorrect

Boiler thermostat differential incorrect

External controls not operating correctly

Correct burner rating

Replace boiler thermostat

Check and correct external controls

Oil smells

Blocked flue, fumes on startup

Oil soaked boiler, faulty burner operation, numerous lockouts.

Odour in cabinet, oil leaks from pipework, flexible hoses connections

Check seals/gaskets

Rectify burner operation and lockouts

Rectify oil leaks, replace components if necessary