Glowworm Ultracom 2 30sxi Boiler Fault Codes

Glowworm boilers

 Code Description Cause Solution
F00 Flow heating temperature sensor fault Sensor open circuit

• Check the sensor’s connections.

• Check the wiring harness.

• Check the sensor.

F01 Return heating temperature sensor fault Return heating temperature sensor disconnected See F00 Solutions
F10 Flow heating temperature sensor fault Sensor short-circuit See F00 Solutions
F11 Return heating temperature sensor fault Return heating temperature sensor shorted. See F00 Solutions
F20 Overheating fault Overheating safety device activated (97°C)

Check the operation of the pump.

• Check the wiring harness.

• Check that the flow and return heating isolation valves are open.

F22 Water pressure of the installation (<0.3 bar) Return water valve closed Pump disconnected Leak in the installation

Fill the installation.

• Purge the installation.

• Check the pump connections.

• Check the flow and return heating sensor connections.

• Check that there are no leaks.

F23 Maximum temperature difference reached between return and flow heating Water circulation fault

• Check the flow and return heating sensor connection.

• Check the pump speed.

F24 Water circulation fault Malfunction of the pump (excessively rapid temperature increase) • Check that the flow and return heating isolation valves are open.
F26 Fault in gas valve motor Disconnected or defective cables

• Check the gas valve connections.

• Check the operation of the gas valve.

• Check the operation of the condensate pump (option).

F27 Flame detection fault Abnormal flame detection

• Check the flame detection electrode.

• Check the main board.

• Check the igniter unit.

F28 Ignition fault

No return gas / Insufficient gas flow

Gas valve incorrectly adjusted

Defective firing electrode and flame control /

Defective igniter unit

• Check the return gas circuit (gas valve open).

• Check the observe the flame picture and check the CO2 setting.

• Check the igniter unit connections.

• Check the state of the electrode (corrosion).

F29 Loss of flame during operation See F28 See F28
F32 Incorrect air pressure Incorrect fan speed

• Check the entire flue system.

• Check the fan’s electrical connections.

F49 EBUS voltage fault

Fault in EBUS line

Short circuit in EBUS connector

Check that the eBus controls are fitted and wired correctly
F61 Fault in the main board Gas valve command fault

• Check the main boards connections.

• Check the main board.

• Check the appliance DSN number is correct.

• Reset the appliance.

F62 Fault in the main board Gas valve closure fault SEE F61
F63 Fault in the main board Fault in the main board memory SEE F61
F64 Fault in the main board Rapid fluctuation of return or flow heating sensor. SEE F61
F65 Fault in the main board Excessive main board temperature SEE F61
F67 Fault in the main board Flame signal fault in the main board SEE F61
F68 Fluctuation of flame signal

No return gas / Insufficient gas flow

Gas valve incorrectly adjusted

Defective firing electrode and flame control /

Defective igniter unit

Check the return gas circuit (gas valve open).

• Check the observe the flame picture and check the CO2 setting.

• Check the igniter unit connections.

• Check the state of the electrode (corrosion).

F70 User interface incompatible with the main board Incorrect product code

Check that the appliance DSN code on the screen matches the product code of the nameplate (in the event of a fault and the appliance DSN does not appear, consult menu.d.93 reserved for the code).

• Check the boards reference.

F71 Flow heating temperature sensor fault Flow heating temperature sensor unclipped or defective (no temperature variation)

Check the sensor connections.

• Make sure that the sensor is clipped to the tube.

F72 Permanent temperature difference between flow and return heating sensors Mismatch between the flow and return heating temperatures (permanent difference)

• Check temperature sensors connections.

• Replace faulty sensors.

F73 Heating circuit pressure sensor fault The sensor is shorted or disconnected.

• Check the sensor’s connections.

• Check the sensor.

F74 Heating circuit pressure sensor fault Fault in pressure sensor SEE F73
F76 Thermal fuse fault Thermal fuse disconnected Defective thermal fuse

• Check the fuses connections.

• Replace the heat exchanger.

F77 Fault in gas valve motor

Defective gas valve.

Defective condensate pump (option)

• Check the gas valve connections.

• Check the operation of the gas valve.

• Check the operation of the condensate pump (option).

F83 No water in the installation : the temperature does not increase when the burner is lit Return water valve closed Pump disconnected Leak in the installation

Fill the installation.

• Purge the installation.

• Check the pump connections.

• Check the flow and return heating sensor connections.

• Check that there are no leaks.

F84 Permanent temperature difference between flow and return heating sensors Inverted or disconnected flow and return heating temperature sensors Defective temperature sensors

• Check temperature sensors connections.

• Replace faulty sensors.

F85 Flow and return heating sensors fault Flow and return heating temperature sensor connected to same tube • Check temperature sensors connections.
F86 Underfloor heating contact fault Floor heating contact open Sensor disconnected or defective

• Check the sensor connections.

• Check that the sensor is connected to the main board and the shunt is removed.

Err User interface fault Defective user interface

• Check connection from user interface PCB to main PCB.

• Replace user interface.